Thermafiber® Safing mineral wool insulation products are designed to provide enhanced fire protection in perimeter fire containment systems tested to ASTM E2307, floor and wall penetrations, construction joints, and other firestopping applications. These products are noncombustible, moisture-resistant, non-corrosive, non-deteriorating, mildew-resistant and vermin-resistant. Thermafiber® Safing provides thermal insulation, fire containment, and enhanced acoustical performance in many different UL and Intertek (formerly OPL) listed fire containment assemblies of 1, 2, and 3-hr ratings.
THERMAFIBER® SAFING
Features
- Exceptional performance in Perimeter Fire Containment Systems as tested in full-scale ASTM E2307 systems
- Provides fire containment in rated assemblies
- Fire-resistant to temperatures above 1,093°C (2,000°F)
- Helps conserve energy, reduce greenhouse gas emissions
- Mold-resistant
- Enhances acoustical performance
- Minimum 70% recycled content
- Contributes to credits in several green building programs, such as LEED® and Green Globes®
Standards, Code Compliance
- CAN/ULC-S702.1, Standard for Mineral Wool Fibre Thermal Insulations, Type 1 (Unfaced)
- ASTM C612, Types IA, IB, II, III, IVA
Installation
All firestopping insulation should be installed per the tested and listed assembly requirements that most closely represent the project conditions.
- Perimeter Fire Containment Installation: Thermafiber® Safing insulation should be compression-fitted between the slab edge and the Thermafiber® FireSpan® curtain wall insulation, leaving no voids per the UL® or Intertek® design listing.
- Penetration Application: Thermafiber® Safing insulation should be cut slightly larger than the opening and compression-fitted into the opening, leaving no voids per the UL® or Intertek® design listing.
- Construction Joint Application: Thermafiber® Safing insulation should be compression-fitted into the joint opening, leaving no voids per the UL® or Intertek® design listing.
Certifications and Sustainable Features
- Verified by ICC-ES to contain a minimum of 70% recycled content. See ICC-ES Evaluation Report VAR-1025 at icc-es.org.
- Environmental Product Declaration (EPD) has been certified by UL Environment. For more information, visit ul.com/epd.
- Safing Products have a published Health Product Declaration (HPD).
Specifications & Literature
Technical Information
PROPERTY | VALUE | TEST METHOD |
|---|---|---|
COMPLIANCE | CCMC Evaluation Listing No. 14060-L | CCMC |
Performance Criteria
PROPERTY | VALUE | TEST METHOD |
|---|---|---|
FIRE | Complies | CAN/ULC-S114 |
| Non-Combustible as defined per NFPA Standard 220 | ASTM E136 | |
| Smoulder Resistance Mean Mass Loss ≤ 0.02% | CAN/ULC-S129 | |
| Flame Spread 0; Smoke Developed 5 | CAN/ULC-S102 | |
| Flame Spread 0; Smoke Developed 0 | ASTM E84 | |
Perimeter Fire Containment | ASTM E2307 | |
Fire Tests of Firestop Systems (Complies) | CAN/ULC-S115 | |
Penetration Firestop Systems | ASTM E814 or UL1479 | |
Material in Construction Joint Systems | UL 2079 | |
MOISTURE | Moisture Absorption <1% by volume | ASTM C1104 |
Water Vapour Permeance; |
| |
CORROSION | Austenitic Stainless Steel - Pass | ASTM C795 |
Steel, Aluminum, Copper - Non-corrosive Types I, II | ASTM C665 |
Perimeter Fire Containment Systems Per ASTM E2307
Safing insulation is a critical component of any perimeter fire containment system. Thermafiber, Inc. has performed decades of testing in all of the perimeter fire containment systems listed below.
- Aluminum Spandrel
- Steel Stud-Framed/Gypsum Sheathing
- Glass Spandrel
- Granite Spandrel
- Precast Concrete Spandrel
- Steel Back Pan
For more complete test information, see UL® and Intertek® (formerly OPL) Directories. For a full listing of fire containment systems, visit thermafiber.com.
UL Reference = TYPE SAF.
For additional job-specific details and accessory materials necessary to complete the Perimeter Fire Containment System, please refer to UL® and Intertek® design listings.2,3
See Owens Corning publication “Enclosure Solutions Perimeter Fire Containment System E2307 Perimeter Technical Bulletin” for more information.
See Owens Corning publication “Thermafiber® Perimeter Fire Containment System Guide” for more information.
Technical Data
PRODUCT | ACTUAL DENSITY | RSI /25.4 MM @ 24 ºC M2•K/W | R-VALUE/INCH @ 75 ºF HR•FT2•ºF/BTU | TEST METHOD |
|---|---|---|---|---|
Safing 4.0 | 64 kg/m3 (4.0 lbs/ft3) | 0.74 | 4.2 |
|
Safing 6.0 | 96 kg/m3 (6.0 lbs/ft3) | 0.74 | 4.2 |
Availability
PRODUCT | AVAILABLE THICKNESS | STANDARD DIMENSIONS4,5 |
|---|---|---|
Safing 4.0 | 25 mm - 178 mm (1" - 7") in | 610 mm x 1219 mm (24" x 48") |
Safing 6.0 | 52 mm (2"), 76 mm (3"), | 610 mm x 1219 mm (24" x 48") |
Tolerances | +6 mm (¼"), -3 mm (⅛") | Width: ±3 mm (⅛"), |
Technical Services Available
For Canadian Technical inquiries, please contact our technical team at owenscorning.ca/contacttech.
Environmental and Sustainability
Owens Corning is a worldwide leader in building material systems, insulation, and composite solutions, delivering a broad range of high-quality products and services.
Owens Corning is committed to driving sustainability by delivering solutions, transforming markets, and enhancing lives. More information can be found at owenscorning.ca or owenscorninglibrary.ca.
Technical information contained herein is furnished without charge or obligation and is given and accepted at recipient’s sole risk. Because conditions of use may vary and are beyond our control, Owens Corning makes no representation about, and is not responsible or liable for, the accuracy or reliability of data associated with particular uses of any product described herein. Owens Corning reserves the right to modify this document without prior notice.
For additional information, refer to the Safe Use Instruction Sheet (SUIS) found in the SDS Database via sds.owenscorning.com.
Applications
- Walls